DMZ-8E Flow Volume Counter
The DMZ-8E Flow Volume Counter is used for dosing or filling preset fluid volumes with two limiting values. This unit also captures the flow rate and can therefore be used as an adjustable flow monitor. A freely configurable current output can be assigned either to the volume or to the speed. Commercially available a flow sensors, which emit pulses proportional to the volume, are used as signal generators. These could be contact-equipped water meters or impeller wheel recorders, for example. Multiple configuration and setting options enable the user to adjust the unit precisely to the given application.
Technical Data
Power supply230 V AC +5%/-10%, 50 Hz
Power consumption
approx. 15 VA
Fuse protection
4 A mT
Inputs
10 V DC,
I approx. 9 mA
Contact resistance: max. 1.5 kOhm
Relay outputs
5 x neutral, max. 230 V AC, 2 A
Current output
0(4)...20 mA, max. load 400 Ohm
Linearity: 0.5% FS
Transmitter
Water meter with neutral contact
or NPN open collector or vane-type sensor with NPN open collector
Transmitter factor
0.01 ... 9999 pulses / liter
max. transmitter frequency
500 Hz (adjustable)
Programmable contact de-bouncing
via maximum sender frequency
Ambient temperature
-20 ... +55 °C
Housing
Control panel housing per DIN 43700
up to IP54, depending on model
Dimensions
W / H / D : 144 x 72 x 116.6 mm
Depth with transparent door: 144 mm
Framing dimensions
W / H : 137 x 67 mm
Ordering information:
DMZ-8E: E1720