LWM-8E Conductance Meter

The LWM-20E is a digital conductance meter with a measurement range of 0 ... 200 mS/cm. The total possible indicating range is captured during measurement (at a probe factor of K=1/cm up to 99.99 mS/cm, for example). In the event the measurement range is exceeded, the unit measures at reduced resolution and precision. Cable capacities up to 50 nF may be masked by means of a special measuring procedure. The unit contains a microprocessor-controlled conductance measurement amplifier, 2 recorder outputs (0)4 ... 20 mA and (0)2 ... 10 V, and two limit value contacts with time delay. A PT-100 input in three-conductor configuration is provided for conductance temperature compensation and for a temperature limit switch. The recorder output can be freely scaled within the entire measurement range (for example, a conductance range of 15 ... 50 mS/cm can be associated to current from 4 ... 20 mA or voltage from 2 ... 10 V). This unit is used in wastewater technologies, water treatment monitoring, desalinization installations, etc.

Technical Data

Power supply
230 VAC +5%/-10%, 50Hz

Power consumption
approx. 7 VA

Measurement input
0 ... 200 mS/cm
Accuracy: better than 1% from final value
other ranges and cell constants available on request

Temperature sensor
PT100 in three-conductor configuration
Temperature compensation
in 0 ... 100°C range,
temperature measurement from -50°C ... 150°C.
Resolution: 0.5K (rounded internally).

Relay outputs
8, max. 230 VAC, 2A,
in 5 neutral groups

Current output
0(4) ... 20 mA, max. load 400 Ohm
Linearity: 0.5% FS

Voltage output
0(2) ... 10 V min. 1 kOhm
Linearity: 0.5% FS
Ambient temperature
-20 ... +55 °C

Housing
DIN control panel housing (IP40),
with transparent cover (optional) IP54
over control panel

Dimensions
W / H / D: 144 x 72 x 125 mm
(incl. connector strip)
Mounting cut-out: W x H: 137 x 67 mm
Installation depth with terminals and connectors
w/o cable, min. 126 mm

Ordering information:
LWM-8E: E2021




pdfdata sheet (german)

pdf description (german)