SYN-7 Synchroniser Relay
The synchroniser relay SYN-7 adjusts voltage and frequency of a generator to the mains, in order to connect it at a minimum difference of frequency and voltage, and at the same phase position. Depending on its configuration, the SYN-7 is monitoring sense of rotation, voltage difference and asymmetry. Voltage measurement is done as 2-, 3- or 4- wire measurement, according to the preset parameterisation. The frequency measurement generally is on L1 and L2. In island mode, the desired frequency and voltage are internally set by the device. A separate variant of the SYN-7 is available for measuring voltages <= 100 V.
Technical Data
Auxiliary Voltage24V DC (18 ... 36 V)
optionally 230V AC / 12 V DC
Power Consumption
approx. 4 W at 24 V DC,
approx. 6 VA at 230 V AC
Digital Inputs
LowActive
(Contact Voltage 12 V, 5 mA,
opto-decoupled), accord. to DIN
Relay Outputs
230 V / 50 Hz / 2 A (potential-free)
Analogue Outputs
0/2 ... 10 V +/- 0.05 V max. 10,5 V
Measuring Range
approx. 50 up to 230 / 400 V,
tolerance < 0,5 % of full scale
( 270 / 480 V )
Frequency Measurement
35.0 Hz up to 65.0 Hz
about approx. 50 V L-N +/- 0.05 Hz
Leading Time
adjustable 50 ... 500 ms
Adjustment Pulses
adjustable 0.1 s up to 100 s
Max. Frequency Difference
adjustable 0.1 ... 1.0 Hz
Max. Voltage Difference
adjustable 1 ... 15 %
Ambient Temperature
-20 ... +55 °C
Housing Dimensions
W / H / D 100 x 75 x 110 mm
DIN top-hat rail mounting 35 mm
Ordering Information:
SYN-7 / 230V AC : E1358
SYN-7 / 24V DC : E1359
SYN-7 / 100V / 230V AC : E1657
SYN-7 / 100V / 24V DC : E1658