SN-4 Level Control
 

SN-4 Level Control

The SN-4 Level Control is a fourfold conductive electrode controller for SPC applications. The antipole for the 4 individual electrodes is at ground potential, so that it can be used as a counter-electrode with metal containers. The response sensitivity has to be adjusted to the conductivity of the switching medium by setting of the potentiometer.

Back to overview

Technical Data

Operating voltage 24 V DC (20 ... 34 V)
Power consumption pprox. 1 W
(w/o external wiring)
Probe inputs probe voltage < 20 V
max. probe supply line > 50 m
(depends on mounting conditions)
Response sensitivity 10 ... 100 kOhm
200 ... 620 kOhm
(activated by: SPS 24V / Cl. 16)
Outputs open collector, PNP
I tot max = 150 mA short-circuit proof
Ambient Temperature -20 ... +55°C
Housing W / D / H : 55 x 75 x 110 mm
(35 mm standard rail)
Download PDF db Data Sheet (german)
  be Description
Ordering information SN-4: E1750