Störmelderelais SMRG-4 und Erweiterungsbaustein SME-12
 

DSR-8 Current Differential Relay

The DSR-8 is a device for measurement and monitoring of differential current at generators, motors and transformers. As well possible is the monitoring of mixed constructions, such as a generator with an upstream transformer. In addition to the differential current, it is also possible to measure the individual conductor currents as well as the earth current in three-wire networks. The connection to the system must be done using external current transformers.

The DSR-8 includes the following protective functions [according to ANSI/IEEE C37.2]: - Protection on differential current for generators, motors and transformers [87GP, 87MP, 87TP] - (Earth-) overcurrent protection [50, 50N, 50G] - Overcurrent-time-protection [51] - Frequency monitoring [81U, 81O]

The comfortable configuration of all settings of the DSR-8 is done by means of the para-meterisation software 'Geräteverwaltung' (GV 2 – Version V2.36 or later required). Alternatively values can be entered directly at the device. Any access to the device's parameterisation can be protected by a PIN. The output of display-texts at the device standardly takes place in German and English (switching between languages is possible at any time during operation). Alternative languages, suitable to the customers requirements, can be configured and conveniently made available, by means of our parameterisation software ''Geräteverwaltung'.


Back to overview

Technical data

Auxiliary voltage 24 V DC (18 – 36 V DC) 230 V AC / 12 V DC *
Power consumption approx. 4 W at 24 V DC
approx. 6 VA at 230 V AC
*on customers request
Digital inputs LowActive
(contact voltage 12 V DC, 5 mA, opto-decoupled) cables not longer than 3 m.
Relay outputs 230 V / 50 cy / 2 A (potential free)
Ambient temperature in operation: -20 … +55 °C transport / storage: -25 … +55 °C
Dimensions W / H / D 100 x 75 x 110 mm
for mounting on 35 mm top-hat rail according to DIN EN 60715
Measurement range approx. 0.02 to 4.0 A AC (1 A Version)
approx. 0.08 to 20.0 A AC (5 A Version)
tolerance < 0.2 % of full scale
Frequency: 15.0 cy up to 100.0 cy
from approx. 150 mA measured
accuracy< 0,01 cy
Download PDF db Data sheet
  beDescription
Ordering information DSR-8 / 1 A / 24 V DC: E1988
DSR-8 / 5 A / 24 V DC: E1990
Accessories

USB A : USB Mini B parameter. cable 1,5 m: KC0215 parameter. cable 3,0 m: KC0329

current transformers, various converter ratios, e.g. 200A/5 A
on request