The synchroniser relay SYN-7 adjusts voltage and frequency of a generator to the mains, in order to connect it at a minimum difference of frequency and voltage, and at the same phase position. Depending on its configuration, the SYN-7 is monitoring sense of rotation, voltage difference and asymmetry.

Voltage measurement is done as 2-, 3- or 4- wire measurement, according to the preset parameterisation. The frequency measurement generally is on L1 and L2. In island mode, the desired frequency and voltage are internally set by the device. A separate variant of the SYN-7 is available for measuring voltages <= 100 V.

Back to overview

Technical data

Auxiliary Voltage 24V DC (18 ... 36 V)
optionally 230V AC / 12 V DC
Power consumption approx. 4 W at 24 V DC,
approx. 6 VA at 230 V AC
Digital inputs LowActive
(Contact Voltage 12 V, 5 mA,
opto-decoupled), accord. to DIN
Relay Outputs 230 V / 50 Hz / 2 A (potential-free)
Analogue Outputs 0/2 ... 10 V +/- 0.05 V max. 10,5 V
Measuring Range approx. 50 up to 230 / 400 V,
tolerance < 0,5 % of full scale
(270 / 480 V)
Frequency Measurement 35.0 Hz up to 65.0 Hz
about approx. 50 V L-N +/- 0.05 Hz
Leading time adjustable 50 ... 500 ms
Adjustment Pulses adjustable 0.1 s up to 100 s
Max. Frequency Difference adjustable 0.1 ... 1.0 Hz
Max. Voltage Difference adjustable 1 ... 15 %
Climatic Conditions acc. to DIN EN 60204-1 ( 05-2010 )
Ambient temperature operation:              -20 ... +55 °C
transport/storage:  -25 ... +55 °C
Dimensions W / H / D 100 x 75 x 110 mm
DIN top-hat rail mounting 35 mm
Download PDF db Data sheet
  be Description
Software Software
Ordering information SYN-7 / 230V AC:  E1358
SYN-7 / 24V DC: E1359
SYN-7 / 100V / 230V AC: E1657
SYN-7 / 100V / 24V DC: E1658